Smartgen Controller HGM6310D for Generator Genset

Smartgen Controller HGM6310D for Generator Genset
PHP 20,033.91
Availability: In stock
SKU
EL1903HW01845038

    Smartgen Controller HGM6310D for Generator Genset

    HGM6310D is an automatic genset controller, which assembles digitization, intelligentization and networked techniques. It is used in automatic and monitor control system of unit set diesel genset to achieve automatic start/stop, data measure, alarm protection and „three remote‟ functions (remote control, remote monitoring, remote communication). The controller adopts large liquid crystal display (LCD) and selectable Chinese and English interface with easy and reliable operation.
    HGM6310D genset automatic controllers adopt microprocessor technique with precision measurement of multi-parameters, fixed value adjustment, time setting and threshold adjusting and etc.. It can be widely used in all types of automatic genset control system with compact structure, advanced circuits, simple connections and high reliability.

    Specification:
    Operating voltage:DC8. 0V to 35. 0V, Continuous Power Supply
    Power consumption:<3W(Standby mode: ≤2W)
    Alternator Input Range:
    3-Phase 4 Wire:20V AC - 360 VAC (ph-N)
    3-Phase 3 Wire:30V AC - 600 VAC (ph- ph)
    Single-Phase 2 Wire:20V AC - 360 VAC (ph-N)
    2-Phase 3 Wire:20V AC - 360 VAC (ph-N)
    Alternator Input Frequency:50Hz - 60Hz
    Magnetic Volt Input Range:1.0V to 24.0V (RMS)
    Magnetic Input Frequency:10,000 Hz (max)
    Start Relay Output:16 Amp DC28V at DC supply output.
    Fuel Relay Output:16 Amp DC28V at DC supply output.
    Auxiliary Relay Output (1-4):
    (1-3)16Amp DC28V at DC supply output,
    (4)16Amp 250VAC passive output.
    Close Generator Relay Programmable Relay Output 5:
    16Amp 250VAC passive
    Close Mains Relay Programmable Relay Output 6:
    16Amp 250VAC passive
    Overall Dimensions:240mm x 172mm x 57mm
    Panel Cutout:214mm x 160mm
    C. T. Secondary:5A (rated)
    Operating Temp. Range:
    Temperature: (-25~70)°C
    Humidity: (20~90)%
    Storage Condition:Temperature: (-40~+70)°C
    Protective Level:
    IP55: when with waterproof rubber ring added
    between controller and its panel.
    IP42: when without waterproof rubber ring between
    controller and its panel.
    Insulation Intensity:
    Object: between input/output/power
    Quote standard: IEC688-1992
    Test way: AC1.5 kV/1min 3mA leakage current