• Automatic Voltage Regulator AVR EA16 400HZ for Generator Genset

    Automatic Voltage Regulator AVR EA16 400HZ for Generator Genset
    PHP 8,395.90
    Availability: In stock
    SKU
    ELFP0403-HD46651460
    Please enter a valid number in this field.
      product page

      Automatic Voltage Regulator AVR EA16 400HZ for Generator Genset

      Specification:
      Kutai  Generator Automatic Voltage Regulator
      Universal 16Amp Self Excited Automatic Voltage Regulator
      for use in 220 / 380 / 440 / 480 VAC brushless generators
      with paralleling compatibility

      1. INTRODUCTION
      Sensing Input
      Voltage 170 ~ 510 VAC, Single Phase 2 wires
      Voltage is DIP Switch selectable
      Frequency 50 / 60 Hz, DIP Switch selectable
      Power Input
      Voltage 60 ~ 300 VAC, Single Phase 2 wires
      Output
      Voltage Max. 90 VDC @ 240 VAC input
      Current Continuous 16A
      Intermittent 20A for 10 sec
      Resistance Min. 5 ohm
      Voltage Regulation
      < ± 0.5% ( with 4% engine governing )
      Voltage Build-up
      Residual voltage at AVR terminal > 5 VAC
      Thermal Drift
      0.03% per °C change in AVR ambient
      Load Current Compensation
      1A or 5A Max. 7% @ PF0.5 DIP Switch Selectable
      Analogue Voltage Input
      Max. ±5VDC. ±10% @ ±3VDC
      Over Excitation Protection
      Max Output DCV 95% 20Sec
      External Volts Adjustment
      ± 5% with 2K ohm 1 watt trimmer
      Unit Power Dissipation
      Max. 10 watt
      Under Frequency Protection ( Factory Setting )
      50/60 Hz DIP SW selectable
      Soft Start Ramp Time

      2 sec.
      Dimensions
      156mm L * 106mm W * 41mm H
      Weight
      450g ± 2%

      The EA16 AVR is an update of the EA15A AVR. It is similar to the original EA15A in power and voltage
      sensing capabilities but with new enhanced paralleling functions; the user can now select the CT inputs either
      1 & 5 Amp or use new A1 & A2 analogue signal inputs terminals for use with PLC paralleling controls. It has
      new over-voltage excitation safety circuits to prevent damage caused by the accidental detachment of the
      sensing wires or irregularities on the generator's excitation circuits.